XM31-915-HP - 10017535
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM31-915-HP
Firmware V2.06.0
Major Alarm No battery;
Self test fail: fast discharge
Minor Alarm OK
Operational Mode Line
Charger Mode Test
Tamper Door closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 119.67 V
Current 9.77 A
Power 996 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 10,086 Wh
Output
Voltage 85.54 V
Power 853 W
Apparent Power 976.86 VA
Frequency 60.00 Hz
Percent Load 76.20 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 11.42 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Enable
Total Standby Events 58
Time Since Last Standby Event 57d 17h:17m
Time in Last Standby Event 0d 0h:16m
Total Time in Standby 290 min
Standby Events Since Reset 34
Time in Standby Since Reset 86 min
Time Since Reset 371 day(s)
Total Run Time 371 day(s)
Transformer Run Time 371 day(s)
Total Downtime 0d 0h:00m
Oil Cap Lifespan Consumed 12.8 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 26 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 
Copyright © 2017-2023 EnerSys. All Rights Reserved.
www.alpha.com   |   www.enersys.com