XM31-915-HP - 10017535
Power Supply
Alarms
Battery
Log In...
English
Español
Français
Português
Deutsch
Overview
Hardware
Power Supply
Batteries
Environmental I/O
Components
Network
Ethernet
Advanced
Interfaces
Network Services
Management
System Data
SNMP
Alarms
Utility Power
History
Power Supply Events
Power Supply Configuration
Battery Events
Standby Events
Alarm Log
d
Power Supply
Model
ALPHA/XM31-915-HP
Firmware
V2.06.0
Major Alarm
No battery;
Self test fail: fast discharge
Minor Alarm
OK
Operational Mode
Line
Charger Mode
Test
Tamper
Door closed
Power Supply Language
English
Power Supply Priority
Normal
d
Input
AC Line Mode
OK
Voltage
119.67
V
Current
9.77
A
Power
996
W
Frequency
60
Hz
Tap Status
Normal
Frequency Range
3.00
Hz
Current Limit
17.00
A
Input Power Consumption
10,086
Wh
1
Output
Voltage
85.54
V
Power
853
W
Apparent Power
976.86
VA
Frequency
60.00
Hz
Percent Load
76.20
%
Output Setting
90 V
Output Regulation
Fine
Over-current Tolerance
3.000
sec
Retry Delay
60
sec
Retry Limit
20
Active Drop Alarm
OK
Active Drop Threshold
50
W
Current
11.42
A
d
Inverter
Inverter Status
Off
End of Discharge Type
String
End of Discharge Level
1.75
V/cell
Reduced Peak Mode
Enable
Total Standby Events
58
Time Since Last Standby Event
57d 17h:17m
Time in Last Standby Event
0d 0h:16m
Total Time in Standby
290
min
Standby Events Since Reset
34
Time in Standby Since Reset
86
min
Time Since Reset
371
day(s)
Total Run Time
371
day(s)
Transformer Run Time
371
day(s)
Total Downtime
0d 0h:00m
Oil Cap Lifespan Consumed
12.8
%
d
Self Test
Deep Discharge Cycle
Timed
Test Countdown
26
day(s)
Test Duration
10
min
Test Interval
30
day(s)
Test Inhibit
No
→ CSV
→ Excel
Copyright © 2017-2023 EnerSys. All Rights Reserved.
www.alpha.com
|
www.enersys.com